XM31-905-HP - 10422586
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-905-HP
Firmware V1.03.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 119.82 V
Current 1.44 A
Power 155 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 7.00 A
Input Power Consumption 9,679 Wh
Output
Voltage 60.61 V
Power 99 W
Apparent Power 122.43 VA
Frequency 60.07 Hz
Percent Load 40.40 %
Output Setting 60 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 2.02 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Enable
Total Standby Events 46
Time Since Last Standby Event 0d 0h:00m
Time in Last Standby Event 0d 0h:00m
Total Time in Standby 333 min
Standby Events Since Reset 6
Time in Standby Since Reset 0 min
Time Since Reset 859 day(s)
Total Run Time 859 day(s)
Total Downtime 4d 20h:18m
Oil Cap Lifespan Consumed 17.8 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 2 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 